Beckett 7505P1515U 120V Genisys Oil Burner Control
Model 7505P 1515 U
Lockout Timing: 15 Seconds
Valve On Delay Timing: 15 Seconds
Motor Off Delay Timing: 15 Seconds
Electrical Ratings
Inputs Voltage: 102 to 132 Vac
Current: 150 mA plus burner motor, igniter, and valve loads
Frequency: 60 Hz
Outputs Motor: 120 Vac, 10 full load amps (FLA*), 60 locked rotor amps (LRA) Note – Reduce motor FLA rating by igniter current
Igniter: 120 Vac, 3 A @ 0.7 PF min
Solenoid Valve: 120 Vac, 1 A @ 0.7 PF min
Thermostat Anticipator Current: 0.1 A (If applicable)
Thermostat Voltage: 24 Vac (If applicable)
The Beckett GeniSysâ„¢ Advanced Burner Control is a 120 Vac primary safety control for residential and light commercial oil burners used in boiler, furnace, and water heater applications. The GeniSys is used with a suitable cad cell fl ame sensor to control the oil burner motor, igniter, and optional solenoid valve. It has 24 Vac thermostat terminals (if applicable) compatible with both mechanical and many power stealing thermostats. It can provide interrupted or intermittent duty ignition, and it has a 15-second lockout time.
Replaces 7457, 7457U, R7184P1064
7505p-1515, 7505p1515